Abstract:To address the corrosion problem of reinforced concrete structures in urban wastewater treatment plants (WWTP)s, 5 urban WWTPs in Fuzhou are selected as the investigation objects. Through on-site investigations and microscopic sampling analysis, the corrosion distribution characteristics, influencing factors and corrosion mechanisms of reinforced concrete structures in wastewater environments are explored. The results indicate that the corrosion of reinforced concrete in WWTPs is mainly concentrated in the pretreatment process sections such as the intake pump rooms and the fine screens. The concentration of H2S gas and relative humidity are the core influencing factors. Enclosed spaces with poor ventilation that lead to the accumulation of corrosive gases will significantly exacerbate the damage. Microscopic analysis confirms that expansion products (ettringite, gypsum) generated from sulfate attack and carbonation are the direct causes of concrete cracking and spalling. Based on the research, the targeted suggestions are proposed in terms of odor removal settings, structural design and maintenance during operation, providing a scientific reference for improving the durability of WWTPs.